Virtual Junction Errors in Temperature
Measurement
What Causes Virtual Junction Errors?
Nearly all thermocouples are manufactured using
magnesium oxide (MgO) as an insulator. As the
temperature of a process increases, the insulation
resistance of the magnesium oxide insulated
thermocouple decreases. Tests of MgO
thermocouples show the insulation resistance may
drop from 1 gig ohm or more at ambient temperature
to 30 ohms or lower at the temperature ranges Type K
or Type N thermocouples are operated.
When the MgO insulation resistance drops to such
low levels, and the thermocouple passes through a
zone at a higher temperature than the point you are
attempting to measure (tube skin thermocouples are a
good example), the measurement point can shift from
the tip of the sensor to the hottest portion of the
thermocouple and give you an erroneous
reading. This is a "virtual"
junction.
AccuTru Solves the Virtual Junction Error
Problem
AccuTru has solved the virtual junction error
problem with its proprietary MI-Dry insulated
thermocouples. MI-Dry is a new formulation of
mineral insulation with properties that
significantly improve thermocouple
performance.
MI-Dry has several advantages over MgO. It
is significantly less hygroscopic, has better
electrical insulating properties, and MI-Dry traps,
slows, and/or prevents contaminating ion movement
through the dielectric resulting in longer sensor
life.
The MI-Dry dielectric exhibits significantly
higher insulation resistance at elevated
temperatures when compared to MgO. In addition
to providing longer life and greater signal
stability, MI-Dry reduces or eliminates virtual
junction errors in thermocouples.
Test Results
Test data in the graph below shows that virtual
junction error was present for the MgO sensor almost
immediately after the test started, but the MI-Dry
sensor continued to read true temperature.

After 100 Hours
- The MgO sensor was reading 10%+ high.
- The MI-Dry sensor was reading correctly.
After 400 Hours
- The MgO sensor was reading 19%+ high.
- The MI-Dry sensor was reading correctly.
Test Protocol for Determining Virtual Junction
Error
The test to determine the susceptibility of
mineral insulated cable to virtual junction error is
quite simple. It requires two furnaces and a means
of measuring the temperature in each furnace and the
temperature output from each test thermocouple.
The center sections of the test thermocouples are
coiled and placed in the mid-section furnace, with
the tips exiting the end of the furnace. A reference
thermocouple is placed in this furnace to measure
the temperature of the coils. The tips of the test
thermocouples and a 2nd reference thermocouple are
wired together to create a thermally conductive
mass. These tips are placed in second furnace.

The temperature of the furnace that contains the
tips of the sensors is then heated to a set
temperature, in this example, 1500 degrees F.
The readings are then taken for the test and
reference thermocouples. All the readings should be
within the limits of error for that type of sensor.
Once the temperature of the tip furnace has
stabilized, the mid-section furnace is started and
the temperature increased to a setting higher than
the furnace containing the thermocouple tips. If the
insulation of a thermocouple fails, the temperature
reading reported for that sensor will begin to
increase, reflecting the temperature in the mid
section furnace rather than the temperature reading
from the tip of the sensor.
This test protocol was used for the test results
reported which show that MgO insulation failed and
MI-Dry did not.